OutageID |
SiteID |
Failure Type |
Start Date |
End Date |
Description |
Resolution Description |
931 |
tci |
Hardware - Instrument |
2024-10-16 14:30:00 |
2024-11-16 19:00:00 |
Radar DSP interface card errors |
Issue resolved during site visit |
922 |
tci |
Hardware - Air Conditioner |
2024-08-01 21:06:08 |
2024-08-15 16:08:00 |
Equipment powered off due to cooling issues |
AC repaired during on-site visit |
920 |
tci |
Hardware - Air Conditioner |
2024-07-19 22:00:00 |
2024-07-29 18:00:00 |
Air conditioner issue; UPS temperature 130 F; all equipment powered off to prevent damage |
Air conditioner repaired |
875 |
tci |
Hardware - Instrument |
2023-08-17 21:30:00 |
2024-05-02 23:00:00 |
Radar antenna malfunction |
Antenna replaced |
862 |
tci |
Hardware - Air Conditioner |
2023-07-16 23:00:00 |
2023-07-26 15:30:00 |
Air conditioner malfunction; equipment powered off until issue is resolved |
Air conditioner replaced |
839 |
tci |
Hardware - PC |
2022-12-31 02:00:00 |
2023-04-14 01:30:00 |
Radar transmitter issue |
Transmitter repaired/replaced |
798 |
tci |
Power Failure |
2022-01-06 01:00:00 |
2022-01-19 19:00:00 |
Power outage due to power-line issues in the area requiring repair by PG&E |
Power restored |
787 |
tci |
Hardware - PC |
2021-09-10 04:00:00 |
2021-10-07 18:00:00 |
Radar computer down |
Computer restarted during site visit |
754 |
tci |
Hardware - Instrument |
2021-01-05 00:00:00 |
2021-08-31 20:00:00 |
Tipping bucket grossly under-reporting precipitation amounts; begin time of malfunction unknown |
Unclogged. Precipitation reported between 16 UTC and 20 UTC on 2021-8-31 was from testing. |
745 |
tci |
Hardware - Instrument |
2020-10-26 05:00:00 |
2021-08-31 19:00:00 |
Propeller vane anemometer malfunction |
Repaired on site |
690 |
tci |
Hardware - Instrument |
2020-02-14 19:30:00 |
2020-03-03 02:30:00 |
Can't connect to GPS Trimble receiver |
Connection re-established during site visit |
664 |
tci |
Hardware - PC |
2019-10-27 19:00:00 |
2020-02-23 23:00:00 |
915-MHz radar PC is non-responsive after UPS power cycle |
PC and radar computer cards replaced |
653 |
tci |
Power Failure |
2019-10-15 05:00:00 |
2019-10-24 01:00:00 |
UPS returned in an power-off state after a suspected power outage; UPS network/web card failure |
UPS network card replaced; UPS powered on |
628 |
tci |
Power Failure |
2019-02-18 23:00:00 |
2019-03-12 02:00:00 |
Can't reach cellular router. Power issue confirmed. |
Power-equipment issue resolved during a site visit. |
619 |
tci |
Hardware - PC |
2019-01-28 00:00:00 |
2019-02-11 20:00:00 |
Radar wind profiler PC issues. |
Windows repair at startup required via user intervention. |